Re: Can't address pull stationsight 5808 on Silent Knight panel.
"Just Some Guy" <notarealaddress@xxxxxxxx> wrote in message
news:ThYEj.317$VK4.118@xxxxxxxxxxx
> Wire up a base to the SLC program terminals. Insert a new smoke detector
> in the base and use the front panel menu to "assign" it an address.
> Repeat as necessary using a different unused address for every new smoke.
> The SLC program terminals are only intended to assigning addresses to
> smokes/heats. You connect the field wiring to the SLC out terminals.
>
> Pulls, monitor modules, control modules, etc get their addresses via dip
> switches.
>
> We like to leave a base connected to the program terminals in case a tech
> needs to add or replace a smoke.
>
> PS I hate SK addressable panels and consider them junk.
>
>
I use the SK addressable panels for most of the Fire jobs I do, I've had no
real problems with them, What problems have you had that make you consider
them junk?
Doug