paul@xxxxxxxxxxxxx wrote:
> On Mar 21, 1:41 pm, "p...@xxxxxxxxxxxxx" <p...@xxxxxxxxxxxxx> wrote:
>> Can't address pull stationsight 5808 on silent Knight panel.
>>
>> Boy, am I frustrated!!.. Manual says just hook unit to 2 terminals
>> named SLC program, follow menu instructions and the unit is
>> programmed. I keep getting "connecting to device" but it never does!!
>>
>> What am I doing wrong?
>>
>> I have the correct +on SLC on panel and SLC on Unit.
>> I have the pull station address set for 1.
>>
>> Any suggestions for what I can do?
>>
>> PS Silent Knight tech support closed for Easter today. Thanks
>
> Model number of pull station is SD 500 Ps
> This is a new panel. I am tryiny to set 1 pullstation to address 1.
> I have verified correct polarity
> The panel has 3 sets of SLC terminals.
> ...SLC in (I am not using)
> ...SLC out (I am not using at this time. Manual sys to connect to SLC
> Program to address)
> ...SLC Program. IO am using these terminals
> Side Note: I do not have voltage at SLC Program terminals but I do
> have voltage on SLC Progam terminals
>
Connect the pull station to the SLC "out" terminals. Observe proper
polarity. You won't have a problem.