arnie <parvezat6@xxxxxxxxxxxxxx> wrote:
>yes i forget to mention about RF transceiver module RTM75 it is also
>in the circuit. As mentioned in your if through this transceiver the
>lamp module is getting turned on then why the PLC is not getting any
>feedback of the transceiver activity. I have tried connecting it both
>in the same phase as PLC as well in another phase. Though the lamp
>module gets turned ON on motion detction but i do not see anything in
>the PLC command window related to this
>Thanks
>Arnie
The most likey explanation is that the TM751 (?) is on one phase and the PLC
is on another. As I posted before, the Signalincs repeat Insteon commands
between phases but they do not repeat X-10 commands.