Re: New Home Construction
> You noticed it's North Carolina but nobody seems
> to have noticed it's on four floors. I think conduit
> is a must.
Having wired systems into existing homes with four or more levels I
disagree. Conduit is a plus on multi-story runs but it's not an absolute
must. If you do opt for conduit, make certain you provide pulling elbows,
junction boxes or LB's at least every 180º of bends -- 90º if the runs are
long. Also, do NOT fill the conduit with more than a 40% cross-section with
copper. There are conduit fill charts available online at several cable
manufacturers' websites, as well as in the NEC manual.
--