[Message Prev][Message Next][Thread Prev][Thread Next][Message Index][Thread Index]
Re: Telco Line Fault??
"nick markowitz" <nmarkowitz@xxxxxxxxx> wrote in message
news:8274b13b-9bf6-4ebb-afd2-2b323fa1c632@xxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
On Apr 26, 8:32 pm, Jim Rojas <jro...@xxxxxxxxxxxx> wrote:
> ABLE1 wrote:
> > "Jim Rojas"<jro...@xxxxxxxxxxxx> wrote in message
> >news:4GpBn.93884$kj3.4119@xxxxxxxxxxxxxxx
> >> ABLE1 wrote:
> >>> Hey to all,
>
> >>> I installed a new Fireworx FX-64RD panel a couple of months ago.
> >>> Almost
> >>> from day one started to receive sporadic Telco Line Faults. Both Line
> >>> 1
> >>> and
> >>> Line 2. Little correlation can be determined except it happens 9 times
> >>> out
> >>> of 10 during the week Monday - Friday and during the day 9am to 5 pm.
> >>> In
> >>> other words 90% of the time during working hours. (aka when the phone
> >>> are
> >>> likely to be used)
>
> >>> It happens 1 to 3 times in a given day and then skip a day or two.
>
> >>> It was originally connected to their Line 1 and Fax Line, I have moved
> >>> to
> >>> L-1 and L-3 no help. It is now on L-1 and L-2 and am waiting to see
> >>> how
> >>> it
> >>> goes. Line 1 happens less frequent so I have left it alone.
>
> >>> In calling UTC Tech Support........................... I was told that
> >>> the
> >>> threshold voltage is 10vdc.
>
> >>> I have gotten the 10vdc from a couple of different techs so that must
> >>> be
> >>> the
> >>> number but it seems to be on high side. I remember on a burg panel
> >>> that
> >>> I
> >>> was having a problem a couple of years ago I was told the threshold
> >>> was
> >>> 6vdc.
>
> >>> What I am reading at the panel is 6.5 to 7.5vdc when a phone is off
> >>> hook.
> >>> So if the threshold is 10vdc then the panel is going to go into
> >>> trouble
> >>> after the timeout of 2 minutes which is the maximum.
>
> >>> The lines that I am working with are (what I think is) POTS lines on
> >>> copper.
> >>> However I was told that if there is a digital converter?? it could
> >>> cause
> >>> some trouble. How do I determine if this is the case???
>
> >>> Has anyone here experienced this?? Especially on this panel??
>
> >>> Any additional thoughts that may help would be appreciated.
>
> >>> TIA
>
> >>> Les
>
> >> Do you have these connected for proper line seizure?
>
> >> Jim Rojas
>
> > Jim,
>
> > Yes, I have RJ31X's on both lines.
>
> > Thanks for thinking on this.
>
> > Les
>
> Check Viking's website. They might have something to help boost the line
> voltage.
>
> Jim Rojas
Improper / dirty grounding can cause line fault problems double check
your grounds.
Nick & Jim,
Are you guys thinking that 6.5 and 7.5vdc is really low?? Or is the 10vdc
threshold high??
What values have you seen with off hook voltages??
Thanks,
Les
alt.security.alarms Main Index |
alt.security.alarms Thread Index |
alt.security.alarms Home |
Archives Home