I have beating my head againts the wall trying to figure this out.  I have a
Power632 and a DSC Pet Immune PIR hooked up to Zone 2.

I have zone 2 set to zone type [04] which is said to be an interior in the
manual.  When I put a ohm meter up to the common and zone 2 pins on the
alarm witht he motion hooked u I get .00 with the meter set to 200 ohms and
then when someone walks in front of it the ohm meter spikes.  This tells me
the motion sensor is working correctly as a closed circuit.  The problem is
that the alarm panel says that zone 2 is open all the time, no mater if the
motion sensor is on or off.  If I short out zone 2 with the commom with a
resistor it shows on the panel that the zone is closed.

What am I missing here?

Thanks!