Re: Power 632 and Motion



>I have beating my head againts the wall trying to figure this out.  I have a Power632 and a DSC Pet Immune PIR hooked up to Zone 2.
>
> I have zone 2 set to zone type [04] which is said to be an interior in the manual.  When I put a ohm meter up to the common and
> zone 2 pins on the alarm witht he motion hooked u I get .00 with the meter set to 200 ohms and then when someone walks in front of
> it the ohm meter spikes.  This tells me the motion sensor is working correctly as a closed circuit.  The problem is that the alarm
> panel says that zone 2 is open all the time, no mater if the motion sensor is on or off.  If I short out zone 2 with the commom
> with a resistor it shows on the panel that the zone is closed.
>
> What am I missing here?

Place an End Of Line (EOL) resistor in series with the zone wiring inside the motion detector.

--