Re: All zones showing fault (NX-8E), please help



NeonTide wrote:
> On May 14, 1:51 am, Frank Olson <Use-the-email-
> li...@xxxxxxxxxxxxxxxxxxxxxx> wrote:
>> NeonTide wrote:
>>> Hi all!  I have a Caddx NX-8E with NX-216E Zone Expansion module and
>>> two NX-148E keypads.  I have programed the system using the DL900
>>> software, but every zone (21 of them) are showing fault.  I'm not sure
>>> if I've missed something in the setup or what.  Any thoughts/
>>> suggestions would be greatly appreciated.  I have put EOL Resistors on
>>> all unused zones and have turned off box tampering as well.
>> It all depends on how you've connected your circuits.  If you haven't
>> used the supplied EOL resistors, then you have to program the panel for
>> "No EOL".
>
> Thank you very much for your help.  I found out where to turn off the
> EOL in the DP900 software.  Now everything works great!

if you knew that eol were needed and put them on the unused zones, why
not put them on the zones that were used?