Re: Fire Alarm System Inspections. How and how much?
> Elevator recall in my area is controlled by ANSI/ASME code and tested by the state elevator inspectors. However, an AHJ can
> require whatever he wants. If he wants a general alarm to recall elevators, then he gets it. The state elevator inspector is
> testing lobbies, shaft and equipment room devices and he doesn't care what else recalls the elevator. Remember that what code
> requires is a MINIMUM requirement and the AHJ is free to require more if they so desire.
>
> As far as duct detectors, code allows them to be programmed as a supervisory device but they MUST shut down their associated air
> handler on alarm. I have several towns where the local officials insist that they be programmed as supervisory. Not all
> addressable fire panels support smoke detectors as supervisories, so this sometimes becomes a problem for us.
>
> My 2 cents.
That was more like your $1000 worth. The above is completely accurate.
--