Re: GE Concord



Thats what I did, I set up zone 1 and 8 for entry exit. and zone 2,3,4 for
interior zones. 5,6,7 are perimeter but when I run a test the central only
gets an alarm 850 with no zone numbers. :(

James


"Sean Sokoly" <alarmdude01@xxxxxxxxx> wrote in message
news:ZTJJf.1439$u54.336@xxxxxxxxxxx
>J Barnes wrote:
>> I installed my first GE panel today.  I was not able to get the zones to
>> report to the CS though.  It would only send an alarm on zone 850.  I was
>> trying to send alarms on zones 1-5.  I am using contact ID.  Is there a
>> place to put the report codes in for the zones?
>>
>> James
> What sensor group did you assign to zones 1-5? There is no way to assign
> report codes. The sensor group assigns a CID Event Code or SIA event code
> that pertains to the sensor group that is selected in learn zones. IE Zone
> 1 Might be basement windows etc you assign Sensor Group 13 (Perimeter
> Burglary) to it under the Sensors Menu it would then report a
> 130 CID Burg Event then the zone.
>
> Sean