Re: Vsita 15P programming question
>> ...In the case of a door contact ...
>
> To carry this one step further, then it would mean
> the EOLR would be in series instead of being in
> parallel with the last device on the line?
Yes, that is correct.
> If that's the case, then it would make no difference
> if the EOLR is at the last device or in the can.
No, that is not correct. If the zone is shorted out between the can and the
last device and the resistor is at the last device the zone would show
either a "trouble" or "alarm" state, depending on the arming status of the
system. If the same thing were to happen with the EOLR in the can the zone
would show "normal".
--
Regards,
Robert L Bass
=============================>