Re: Ademco:PanelDumpsCentralStation



With the Vista50P, you have to do it manually.

Location 32 is the Account number (enter 15 15 15 15)
Location 35 is the call back number
Location 36 is the CSID (enter 15 15 15 15 15 15 15 15)
Location 37 enables download (enter 11011111) last 2 digits enable upload &
download
Location 153 to disable call back (enter 0)

When you call the panel select first time communication with default account
number, no call back. This way you are guaranteed to get into the panel.
Once you are connected to the panel, upload all data, make your changes,
then download to panel. Compass will automatically insert the proper account
number.

I suggest you select Ademco Contact ID as the format. Also on the bottom of
the screen, Compass can insert all the default Contact ID codes
automatically. This is handy and will save you some time. You still however
must enable signals like Low Battery, Tests, Cancel, Exit Error, etc...its
all on one screen.

Jim Rojas

"Crash Gordon" <webmaster@xxxxxxxxxxxxxxxxxxxxx> wrote in message
news:qmT%e.4$nm5.527@xxxxxxxxxxxxxxxxxx
> Mark says it doesn't do that on a 50P. I don't use 50Ps.
>
>
> "James" <trishnjames@xxxxxxxxxxx> wrote in message
> news:8KadnYIef_OE86LenZ2dnUVZ_sydnZ2d@xxxxxxxxxxxxxx
> | *96 wipes the account number and resets the CSID code for a first time
> | communication.
> |
> | James
> |
> | "Crash Gordon" <webmaster@xxxxxxxxxxxxxxxxxxxxx> wrote in message
> | news:XlI%e.134$Mx2.11093@xxxxxxxxxxxxxxxxxx
> | > Forget the *96 I was thinking of smaller panels.
> | >
> | > If you're doing commercial fire I suggest you get a qualified
> installer
> to
> | > finish your job - or you may never pass inspection.
> | >
> | >
> | > "Don" <dgp0@xxxxxxxxxxxxx> wrote in message
> | > news:1128219617.693817.322540@xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
> | > | Mssrs. Gordon and Rojas,
> | > |
> | > | I do not know my transmission format.  I believe it to be the
> default.
> | > | I believe the default is Ademco low speed.
> | > |
> | > | I do not know the central station's receiver kind.
> | > |
> | > | Each smoke is on its own zone.  I have not definitively worked out
> the
> | > | amperage but I have another 12-volt, 7-amp ready to wire to the
> panel
> | > | in parallel with the first, if that is the correct thing to do.
> | > |
> | > | Security system is part of an ongoing building renovation project.
> | > | Project has new insurer.  Insurer demands site be telephone
> monitored
> | > | or they will drop me.  The problem has persisted for three months!
> | > | They are tired of waiting for compliance.
> | > |
> | > | I will get back to the site on 03Oct05.  I will
> | > | 01 go to Section 1*53  and enter 0.  If that does not work, I will
> do
> | > | as you both recommend and
> | > |
> | > | 02 wipe the account number.
> | > |
> | > | 03 For "First time communication" I will re-program the same account
> | > | number, primary and secondary telephone numbers with the same
> numbers
> | > | (?!) I just wipe.  Then I will call the central station and ask them
> to
> | > | try again.
> | > |
> | > | What is *96?
> | > |
> | > | Thanks for the guidance.  I hope it works.  I will let you know,
> either
> | > | way.
> | > |
> | > | Thanks again.
> | > |
> | > | Don
> | > |
> | >
> | >
> |
> |
>
>