Re: Firelite MS5024UD



"Mark Leuck" <m..leuck@xxxxxxxxxxx> wrote in message
news:E66dndpALJLDHs3enZ2dnUVZ_tOdnZ2d@xxxxxxxxxxxxxx
>
> "Bob La Londe" <usenet@xxxxxxxxxxxxxxxxx> wrote in message
> news:Q7udnd7F0Ydy883eRVn-rg@xxxxxxxxxxxxxxx
>>
>> "Mark Leuck" <m..leuck@xxxxxxxxxxx> wrote in message
>> news:FvSdnWk1sZjTqc3eRVn-pg@xxxxxxxxxxxxxx
>> >
>> > "Bob La Londe" <usenet@xxxxxxxxxxxxxxxxx> wrote in message
>> > news:7bqdnZH7I-qRXNLeRVn-jA@xxxxxxxxxxxxxxx
>> >> I forwardew Marks Comments to the Firelite tech I have been dealing
> with
>> >> last night.  So far no repsonse this morning.
>> >>
>> >> How ever his last messenge the day before yesterday said.
>> >>
>> >> "When a panel locks up, or if the lines stay latched or always on, it
> is
>> >> usually due to a non-UL listed receiver compatible with our panels. It
> is
>> >> quite common."
>> >>
>> >> --
>> >> Bob La Londe
>> >>
>> >> Cheapskate's Ways to Do Fishing Stuff
>> >> (The Frugal Fisherman)
>> >> Through the Month of October 2005
>> >>
>> >> http://www.YumaBassMan.com
>> >
>> > I'm sorry but that is total bullshit, I have NEVER heard of a panel
>> > locking
>> > up because of a receiver.
>> >
>> > BTW What format are you using?
>> >
>>
>> CID
>>
>> I may try 4 X 2 if I can't isolate the problem.
>>
>> The tough part is I have done a complete inspection and test ont his
>> panel
>> per NFPA four times now.  Everything tests out just perfect.
>>
>> --
>> Bob La Londe
>>
>> Cheapskate's Ways to Do Fishing Stuff
>> (The Frugal Fisherman)
>> Through the Month of October 2005
>>
>> http://www.YumaBassMan.com
>
> Can't hurt but did FireLite say this (bogus) problem only happens with
> CID?
>
>

Not exactly, but the tech guy specificaly mentioned CID " Not every receiver
that is "Contact ID" compatible is going to work with every panel. " in one
of his e-mails.  I figured there is a reason for that.  He also suggested
using 4X2 " I would try other formats to see what works and is received fine
by the central station, something like 4+2 format." standard in another as
an option when I asked if siwtching to a pulse format would solve the
problem.  Of course I had never told him what format I was using in the
first place so, I assumed there was a reason he mentioned CID specifically.

--
Bob La Londe

Cheapskate's Ways to Do Fishing Stuff
(The Frugal Fisherman)
Through the Month of October 2005

http://www.YumaBassMan.com