Re: need help with Northern N-1000-IV panel



Sounds like a reader issue. What bit set do you have the reader data set to?
If memory serves me, the panel default is 37 bit. If you're using a 26 bit
standard reader...there's your problem. Check your card format information.

"alex rogozin" <arogozin at comcast period net> wrote in message
news:4J-dnUIAd_LLys3eRVn-iA@xxxxxxxxxxxxxx
> i did buffer, unbuffer, initialize, re-created databases and created new
> ones as described in described order.
> from "Panel Control" relay energizes, de-energizes, pulses fine.
> the readers i use are HID  ProxPro 2, cards are 5 digit HID. The reader
> board pulses as described during card read. "reverse LED" under panel -
> readers does not work.
> reader issue ? my next step is to get mag reader and try that one.
> If someone could post or email working backup of the system i could also
try
> that approach.
>
> Thanks to all reading this and trying to help.
> Regards,
> Alex
>
>
>
> "petem" <petem001@xxxxxxxxx> wrote in message
> news:l0W3f.22724$Tn2.456984@xxxxxxxxxxxxxxxxxxxxxx
> > did he unbuffer the panel at log on?
> >
> >
> > "alex rogozin" <arogozin at comcast period net> a écrit dans le message
de
> > news: 0v-dnZzls4MQntLeRVn-iQ@xxxxxxxxxxxxxx
> >> I'm not even getting invalid card reads - bad panel ?
> >>
> >>
> >> "Jackcsg" <nospam@xxxxxxxxxx> wrote in message
> >> news:us2dneOkWeItJdreRVn-vw@xxxxxxxxxxxxxxx
> >>> Check your Time Zones. Sounds like you're getting invalid card reads.
> >>>
> >>> "alex rogozin" <arogozin at comcast period net> wrote in message
> >>> news:6YednXO5GeB-XdjeRVn-rg@xxxxxxxxxxxxxx
> >>>> need help with setting up 1000-4 panel - v8.02 win-pak 1.17 connected
> >>>> through serial, HID prox receiver, HID cards.
> >>>> created databases, did everything by the manual ( or maybe missed
> >>>> something ) - panel control works fine, relays energize, panel appear
> >>>> to
> >>>> work. On card read green light on the 4-reader board goes steady for
> >>>> 1/2
> >>> sec
> >>>> as described - no messaged in win-pak and no relay action - what did
i
> >>> miss
> >>>> ?
> >>>> Any help appreciated.
> >>>> Also - will any RS232 to RS485 converters work or i must get Northern
> >>> C-100
> >>>> or N-485 ?
> >>>>
> >>>> Regards,
> >>>> Alex
> >>>>
> >>>>
> >>>
> >>>
> >>
> >>
> >
> >
>
>