[Message Prev][Message Next][Thread Prev][Thread Next][Message Index][Thread Index]
Re: Vista 20p installation problem
Short zone #1 for alarm, open zone #1 for trouble.
"eric" <eerixx@xxxxxxxxx> wrote in message
news:1116792471.559552.288380@xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
>I programmed zone-1 as "Fire" but when I trip the zone the buzzers on
> the
> keypads go off and it says "fire trouble" but the Siren does not go
> off. The
> siren does work for other zones but not with zone-1. Fire siren Time
> outs is
> set to default. What's the problem?
>
> If I was to add more sirens can I put 2 or 3 sirens in parallel?
>
> Thanks!
>
alt.security.alarms Main Index |
alt.security.alarms Thread Index |
alt.security.alarms Home |
Archives Home