Re: Napco P9600 - Smoke Alarm Reset



On Monday, 20 September 2021 at 22:05:09 UTC-6, alar...  wrote:
> On Monday, September 20, 2021 at 11:16:26 PM UTC-4, Medtech1 wrote:=20
> > Thanks for the reply... I do have the smoke detector powered by termina=
l 28 (+) and 29 (-) but hitting reset on the keypads doesn't seem to interr=
upt the power.
> How many smoke detectors and are they 4 wire or two wire smokes? And who =
is the manufacturer? Are these smokes on the list of acceptable smoke detec=
tors?

They are 4 wire smoke detectors... ESL TS7-4 (https://edwards-signals.com/f=
iles/700_Series_Smoke_Install_13083-EN.pdf) described as:

Head with base (sold together)=20
TS7-4 Four-wire photoelectric smoke detector with alarm relay=20
(NO) output and remote alarm/trouble LED output=20

The installation instructions for the TS7-4 state:  "To reset the detector,=
 follow the control panel=E2=80=99s reset procedure. Resetting the control =
panel will remove power from=20
the detector and allow it to reset."

The P9600 is fairly new.. purchased a year or two ago, but only installed n=
ow. Keypads are new, but I'm not sure the firmware version... but I will ch=
eck this.