The back box is inside the wall. Even so, we tried a version of that. It
ends up getting clogged by the stuff that washer is trying to get rid of.
"Doug" <not@xxxxxxxx> wrote in message
news:KW%Xi.2610$mv3.2515@xxxxxxxxxxxxxxx
> Drill a small hole in the bottom of the back box to provide a drain for
any
> water that finds its way in.
>
>
> Doug
> --
>
> "Roland Moore" <nospam@xxxxxxxxxx> wrote in message
> news:47308815$0$20560$4c368faf@xxxxxxxxxxxxxxxxx
> > There is really not that much to a pull station. It wasn't the device
> > itself
> > that was the problem, although the water blasts didn't help it. It was
the
> > idea that, even with a stopper over it and other protection, the high
> > pressure forced water up into the conduit several feet above the device.
> > Since it was forced into the emt, and the system was sealed, the water
> > stayed in the pipes and soaked the cable and connections to the point a
> > ground would appear on the circuit.
> > Again, since all the connections were water tight, the only way to
remove
> > the ground was remove the device and let the water drain. That is a
> > chargeable service call, and that is what he bitched about.
> >
> >
> > "ren" <ren@xxxxxxx> wrote in message
> > news:og_Xi.28343$N7.5512@xxxxxxxxxxxxxxxxxxxxxxxxx
> >> shoulda used exterior parts in that area. tsk, tsk. nest time try
using
> >> that head for something other than a hat rack. ;)
> >>
> >> "Just Looking" <nospam@xxxxxxxxxx> wrote in message
> >> news:472fa174$0$25640$4c368faf@xxxxxxxxxxxxxxxxx
> >> > Is anyone interested in buying a cheap no good customer or two? I
have
> >> > several I need to unload. One who keeps bitching about how we are
> > ripping
> >> > him off for repeat service calls on a fire alarm trouble signal. I
> >> > continue
> >> > to explain that when you use a high pressure wand to wash the area,
> >> > that
> >> > the
> >> > AV and pull station emt will fill with water.
> >>
> >>
> >
> >
>
>