Re: Anyone work with foam systems



Frank sent it to me.  It's the reason why you shouldn't even "go there"
unless you've got damn good liability coverage and the place is EMPTY.


"Crash Gordon" <webmaster@xxxxxxxxxxxxxxxxxxxxx> wrote in message
news:4557ced7$0$25785$815e3792@xxxxxxxxxxxxxxxxx
> You ever see those pix of the foam "test" at a hanger? Extremely funny. I
> think someone posted a link to it here about a year ago.
>
>
> "FIRETEK" <firetech(change-the-ch-to-k)@telus.net> wrote in message
> news:TnP5h.6619$ae6.6120@xxxxxxxxxxx
> | To expand a bit upon Frank's post, manufacturer's training helps but
> | certainly isn't mandatory.  Inspection usually involves disconnecting
the
> | squib or solenoid valve and ensuring all the initiating devices
annunciate
> | at the panel, the programmed release sequence is initiated, and the
panel
> | provides the proper output to discharge the system and shut down
required
> | devices.  It's also a good idea to test the "cancel discharge" functions
> | which will only work if an automatic intiating device (heat, smoke, or
> flame
> | detector) is activated.  The "manual discharge" will do exactly that,
> | usually with no chance for user intervention once activated (although I
> have
> | seen it done in one large hangar, but that one was "weird").  On the
> | mechanical side, you have to weigh the cylinders, check pressures,
> nozzles,
> | etc.  One more thing.  Before you initiate any testing, make sure to
move
> | valuable equipment away from the area.  It's not a good idea to flood
> | someone's nice expensive Learjet with foam (although I hear it cleans up
> all
> | bright and shiny).  :-)
> |
> |
> | "Frank Olson" <Use_the_email_links@xxxxxxxxxxxxxxxxxxxxxx> wrote in
> message
> | news:dwm5h.290326$1T2.219579@xxxxxxxxxxxx
> | > nick markowitz wrote:
> | > > Have a petro customer where i just changed out a releasing panel for
> | there
> | > > foam system which protects the gasoline loading rack.  They said
they
> | are
> | > > having an extremely hard time getting techs to service there
national
> | foam
> | > > system any one familar with what it takes to fully inspect and
cerify
> | them.
> | > >
> | > >
> | >
> | >
> | > Yup.
> |
> |
>
>