Doug L wrote:
> I think the NFPA 72 requirement is that the system alternates its daily test
> between the two lines.
>
> Doug
>
My copy of NFPA 71 doesn't mention that. It only states that "each DACT
shall automatically initiate and complete a test signal transmission
sequence to its associated DACR at least once every 24 hours." AFAIK
that remains the only requirement other than the one that states that
failure of a telephone line shall be annunciated locally and transmitted
to the DACR within 4 minutes on the second (backup) line.