Re: Fire Alarm Signal Xmission
why take the chance of going through a channel bank, just have the client
buy a pots line for the primary...or ask the people who installed the
channel bank to add you as additional insured to their liability insurance.
"Nick Markowitz" <nick-markowitz@xxxxxxxxxxx> wrote in message
news:fpcEf.4171$pO2.3421@xxxxxxxxxxx
| For safety sake the t1 channel bank should have the required 24-60 hors
| battery back up you would follow if it was thru a pbx the nfpa codes have
| not caught up to modern communication techniques.
|
| Also note be careful to check and make sure your format is transmitting Ok
| many times you need to switch to contact id or SIA as 3/1 and 4/2 formats
| will not always transmit correctly thru a channel bank i have had this
| problem especially with choice one service
|
|