[Message Prev][Message Next][Thread Prev][Thread Next][Message Index][Thread Index]
Re: Causes of Ground Faults
On Tue, 19 Dec 2006 01:44:56 GMT, Michael <sirflannelS@xxxxxxxxxxxx>
wrote:
>Let's see....
>
>Wires stripped back too far behind devices touching back box
>
>wires stripped back too far in the control panel
>
>wires pulled tight and tye wrapped or secured around sharp metal
>corners
>
>wires pulled roughly during wiring, causing nicks in the wire
>
>heat detector and pull station in resturaunt kitchens getting sprayed
>down during nightly cleanup
>
>leaky roof above smoke detector
>
>non-weather resistant horn strobe placed outside, moisture getting
>inside box, corroding wire and damaging horn strobe
>
>50 feet of slack crammed into a 4-O box behind a horn strobe getting
>nicked and crushed inside the box
>
>Anyone think of anything I missed ?? <g>
What about the CAT HAIR!!
Does everyone know what I mean by cat hair? It's the fiber that
comes in the jacket... No, Jack.. It ain't complimentary floss!
--
-Graham