Re: Question about SmartHome 1132CU programming
On 4/28/2012 11:14 PM, Harold Sharpe wrote:
> On Apr 28, 5:13 pm, Art Todesco<actode...@xxxxxxxxx> wrote:
>> I have and use a SH 1132CU with the "plus" software. Basically, my
>> house is on house code B, however, some stuff is on C. I have front
>> floods on C10 and rear floods on C9. In the 1132 programming I have a
>> macro that basically says, if B8 goes on, then do a C9 on and a C10 on.
>> Similarly, there is a 2nd macro that says, if B8 goes off, then do a
>> C9 off and a C10 off. However, if one of the manual controllers, set to
>> house code B, does an "all off", the 1132CU doesn't do anything. I was
>> wondering if someone has found a way to program the 1132CU that would
>> basically say, if you do a B, all off, it would recognize that and
>> subsequently do a C9 off and a C10 off. The reason for putting the
>> floods on C9 and C10, was to free up B9 and B10 for other things. Any
>> ideas? Thanks.
>
> There is a set up on the 1132cu plus for the letter all on or letter
> all off
> set it up as
> If B all Off Turn C8 off
> Delay 3 second
> turn c9 off
>
Thanks, I did it and it works. I never looking in the drop downs where
it appears, so I never found it. A 'B All Off', now also does a 'C All
Off. '