Re: Question about SmartHome 1132CU programming
On Apr 28, 5:13=A0pm, Art Todesco <actode...@xxxxxxxxx> wrote:
> I have and use a SH 1132CU with the "plus" software. =A0Basically, my
> house is on house code B, however, some stuff is on C. =A0I have front
> floods on C10 and rear floods on C9. =A0In the 1132 programming I have a
> macro that basically says, if B8 goes on, then do a C9 on and a C10 on.
> =A0 Similarly, there is a 2nd macro that says, if B8 goes off, then do a
> C9 off and a C10 off. =A0However, if one of the manual controllers, set t=
o
> house code B, does an "all off", the 1132CU doesn't do anything. =A0I was
> wondering if someone has found a way to program the 1132CU that would
> basically say, if you do a B, all off, it would recognize that and
> subsequently do a C9 off and a C10 off. =A0The reason for putting the
> floods on C9 and C10, was to free up B9 and B10 for other things. =A0Any
> ideas? =A0Thanks.
There is a set up on the 1132cu plus for the letter all on or letter
all off
set it up as
If B all Off Turn C8 off
Delay 3 second
turn c9 off