[Message Prev][Message Next][Thread Prev][Thread Next][Message Index][Thread Index]

Re: UDACT Programming - Notifier



"Bob La Londe" <none@xxxxxxxxxx> wrote in message
news:lm5g8m$bi3$1@xxxxxxxxxxxxxxxx
> "CVFE" <cvfeinc@xxxxxxxxx> wrote in message
> news:596f4465-df15-41ea-8186-8fe73dea6e48@xxxxxxxxxxxxxxxxxxx
>> I just got a monitoring contact for a business with a Notifier NFS-320.
>> It's monitored now using an AES network. I'm not set up to do AES. Any
>> ideas how I monitor this panel. I'm assuming I need to hook up a UDACT
>> and program it. Any other ideas out there? Thanks for any help!
>
> Throw a TG-7FS cellular communicator on it.  If you can't hit two towers
> use the remote antenna.
>
>
>

I take it there are no phone lines available?

Does the AES network use dialer capture or inputs triggered by the FACP?

If the AES transmitters use inputs then its likely that the OPs Notifier
does not have a UDACT installed in which case I don't think a TG-7 could be
used without installing a UDACT-2 or a slave dialer of some sort to feed
into the TG-7

The DSC 3G3070-CF sole path communicator does dialer capture and also has
inputs that can be triggered by the trouble and general alarm outputs of the
Notifier NFS-320 panel
http://www.dsc.com/index.php?n=products&o=view&id=1402

I recently had to bid on monitoring a Fire alarm that was using an old
Ademco radio,  the panel only had trouble and alarm outputs and no dialer,
my first thought was the TG7 but it didn't have any inputs, only dialer
capture. The only sole path communicator I could find with inputs was the
DSC, so my bid was based on that.

I can't tell you if its any good or not since I didn't get the contract

Doug




alt.security.alarms Main Index | alt.security.alarms Thread Index | alt.security.alarms Home | Archives Home