Re: 2 Partition DSC 1864 Smoke Detector Question
> "alarman" <nospam@xxxxxxxx> wrote in message
> news:50s9k.5739$_T7.2302@xxxxxxxxxxxxxxx
>> Mike Schumann wrote:
>>> I am installing DSC 1864 Alarm Panel with 2 partitions to provide
>>> security in two buildings. I am using 2 wire smoke detectors,
>>> directly connected to PGM2 in the panel in the main building.
>>>
>>> I am running a 4 wire cable to the remote building for the second
>>> keypad and a PC5108 Expansion Module. I also want to put in a couple
>>> of smoke detectors in the remote building.
>>>
>>> What is the best solution for providing smoke detectors in the remote
>>> building? Can I use 4 wire smoke detectors and wire them into a zone
>>> on the PC5108 or do I need to do something else?
>>>
>>> Thanks,
>>
>> Yes, you can use the zone expander. Use fire cable between the main panel
>> and the zonex.
>>
>> --
>> js
>>
>> This space for rent.
>>
"Crash Gordon" <webmaster@xxxxxxxxxxxxxxxxxxxxx> wrote in message
news:48668910$0$87078$815e3792@xxxxxxxxxxxxxxxxx
> how do you do the power supervision relay then?..just curious...it'll eat
> a zone on the expander right (4wire smokey)?
>
>
> --
> **Crash Gordon**
>
>
>
I don't see a problem with the power supervison relay or why it would use
another zone up, if the power to the smoke is lost the zone will show open
just like any other fire zone (assuming a power supervision relay is used) ,
resetting the smoke may be a problem if it is powered from the zone
expander.
Doug