Re: 12V FA



They make a 4 zone adapter which allows 4 additional zones of 2 wire smoke
with the vista panels you can gang them together for multiple 2 wire zones
as long as you do not exceed power supply.


"Frank Olson" <use_the_email_links@xxxxxxxxxxxxxxxxxxxxxx> wrote in message
news:tHWQj.224771$pM4.197437@xxxxxxxxxxxx
> JoeRaisin wrote:
>> Red wrote:
>>> Aren't the bigger Vistas 12V? 128FB?
>>>
>>> On Fri, 25 Apr 2008 08:19:46 -0400, TechMex <bobn@xxxxxx> wrote:
>>>
>>>> Day care needs fire alarm repair.  System is 12V, smokes-12V, strobes
>>>> are 12V gentex.  Anyone know of any 12V commercial rated fire alarms?
>>>> Needs 4 or more zones.  My first thought was to replace everything but
>>>> of course they need to save as much $ as possible for the children so I
>>>> thought I'd ask the pros here.
>>>
>>
>> I would think the Vista 32FB would suit according to what I've read.
>
> That all depends.  If the smokes are two wire, he's going to have to
> confirm compatibility with the Vista panel.  Then there's the other small
> "limitation" in that only the first two zones are capable of powering two
> wire conventional smokes (that goes for both panels).  He actually didn't
> provide much in the way of information to begin with. Hopefully his choice
> will work for him and he *won't* call Bass for technical "support".  :-)