Re: EST1 Compatible Smoke Detectors



Frank Olson wrote:
> Hi Tech wrote:
>> Hello,
>>
>> We've been asked to take over the service of a fire alarm system using
>> an EST1-2Z6 panel. Does anyone know what analog smoke detectors are
>> compatible with this unit? System Sensor doesn't show any and ADI has
>> been no help.
>>
>> Thanks in advance.
>>
>> Mike S.
>> Hi Tech Security, Inc.
>>
>
>
> Here's a complete listing of compatible detectors (with the EST1-2Z6)
>
> System Sensor 1400A (Edwards 1400A)
> System Sensor 2151A (Edwards 2151A) with the EDWB110LP Base only
> System Sensor 1451A (Edwards 1451A) with the EDWB401B, EDWB406B, and
> EDWB406BR Bases only
> System Sensor 2451A (Edwards 2451A) with the EDWB401B and EDWB406B Bases
> only
>
> C2M-PD
> C2M-PDC, C2M-PDHC, and C2M-PDHRC (the "Clean Me" option must be in the
> "OFF" position)


I forgot to add:

Maximum 30 detectors per initiating circuit and you can't "mix" them.