Re: EST1 Compatible Smoke Detectors



Hi Tech wrote:
> Hello,
>
> We've been asked to take over the service of a fire alarm system using an
> EST1-2Z6 panel. Does anyone know what analog smoke detectors are compatible
> with this unit? System Sensor doesn't show any and ADI has been no help.
>
> Thanks in advance.
>
> Mike S.
> Hi Tech Security, Inc.
>
>


Here's a complete listing of compatible detectors (with the EST1-2Z6)

System Sensor 1400A (Edwards 1400A)
System Sensor 2151A (Edwards 2151A) with the EDWB110LP Base only
System Sensor 1451A (Edwards 1451A) with the EDWB401B, EDWB406B, and
EDWB406BR Bases only
System Sensor 2451A (Edwards 2451A) with the EDWB401B and EDWB406B Bases
only

C2M-PD
C2M-PDC, C2M-PDHC, and C2M-PDHRC (the "Clean Me" option must be in the
"OFF" position)