[Message Prev][Message Next][Thread Prev][Thread Next][Message Index][Thread Index]
Re: Napco MA3000 - Dialer Test on both Lines?
The CF5530 two line module for the Napco MA3000 selects the best working
line of the two connected to it to dial out on. You cannot dictate which of
these is to be used for a test. You can, however, program the system to
send a test to a second phone number by programming the test to be sent to 1
and 3. This will test the second central station line, but not the second
phone line connected to the panel. The panel automatically reports a
problem with either phone should one have failed or has a problem.
"Allan Waghalter" <awaghalter@xxxxxxxxxxx> wrote in message
news:bKxug.68411$Lm5.42410@xxxxxxxxxxxxxxxxxxxxxxxxxxxxx
> Does anyone know how to get the MA3000 to send a daily test signal, as
> required by NFPA, on both phone lines. No problem sending test on telco
> 1, just don't know how to make it test on telco 2. On our commercial fire
> alarms, each line calls into a different account number and different
> receiver for each line. We get no test on the second line.
> Thanks,
> Allan
>
>
alt.security.alarms Main Index |
alt.security.alarms Thread Index |
alt.security.alarms Home |
Archives Home