Re: Need Programming assistance on a Notifier SFP-1024 Control



On 07/06/2014 05:36 PM, RTS wrote:
> "Bob La Londe"  wrote in message news:lpclu7$mgj$1@xxxxxxxxxxxxxxxx
>
> "John Sowden" <jsowden@xxxxxxxxxxxxxxxxxx> wrote in message
> news:lp6thf$smf$1@xxxxxxxxxxxxxxxx
>> On 07/04/2014 07:10 AM, RTS wrote:
>>> "John Sowden"  wrote in message news:lp4mtk$neu$1@xxxxxxxxxxxxxxxx
>>>
>>> On 07/03/2014 10:20 AM, Bob La Londe wrote:
>>>> "John Sowden" <jsowden@xxxxxxxxxxxxxxxxxx> wrote in message
>>>> news:lp1q86$i3u$1@xxxxxxxxxxxxxxxx
>>>>> I am receiving 2 daily test signals from the above panel.  Notifier
>>>>> refuses to provide programming assistance, and the manual does not
>>>>> make it clear re: double reporting.  Silent Knight used to have a Must
>>>>> call option, which caused multiple signals, but I figured that out in
>>>>> the 80s.
>>>>>
>>>>> tia,
>>>>>
>>>>> John
>>>>
>>>>
>>>> Some FACP manufacturers have their panels setup so that they can *only*
>>>> send TWO test signals when monitored.  One on each line.  I don't know
>>>> much about Notifier, but they may be that way.  I have a couple of them
>>>> on Sole Path Cellular and the extra air time is annoying, but I do make
>>>> money on them.  I have alarms dialing my own toll free lines, so extra
>>>> call time is only a few cents per signal on those that are on
>>>> landlines.
>>>
>>>> This system is in our LATA so I have it dial into a local phone line.
>>>> My concern is the dispatchers having to deal with 2 phone calls every
>>>> night. This is the only one that does this.  No reference is made in
>>>> the manual to sending 2 signals every day.  Gee, wait for the next
>>>> nfpa 72, we'll be getting 4 signals per day, one every 6 hours!
>>>
>>>> John
>>>
>>>
>>> John  try matching the Notifier panel with a Firelite  panel  ( their
>>> made in the same factory by the same company)
>>>
>>> then  call Firelite with your problem  using the Firelite panel as
>>> reference..
>>>
>>> My experience has been the panels are the same just the names and part
>>> numbers are different..
>>>
>>> RTS
>>>
>>>
>>>
>>> ---
>>> This email is free from viruses and malware because avast! Antivirus
>>> protection is active.
>>> http://www.avast.com
>>>
>> love it, an outside the box thinker!
>>
>> john
>
>> Interesting, I think it was a Firelite panel I first noted what you
>> described.  Dual daily test (one on each line) and no apparent way to
>> change that.
>
>
> your listed  Notifier SFP-1024   seem to be the same as a Firelite
> MS-5-10 (5 zone or 10 zone)
>
> the DACT  programing   "Report Style"  can select     1=backup only,
> 2=both,   3=first available
>
> also in the DACT programing   "Test Time Interval"    1=24 hours,
> 2=12 hours,  3=8 hours  (page 2)   1=6 hours
>
> That might be the place you need to look for changing the dial out...
>
> RTS
>
>
> ---
> This email is free from viruses and malware because avast! Antivirus
> protection is active.
> http://www.avast.com
>
Sorry about the delay to respond.  I am working my email off 2
computers.  I did find the Firelite MS-5510 ? Its on the computer at the
office.  The backup is not the answer, as I would be receiving double
reporting on the alarms during inspections.  I found an entry to send
the daily test to the second phone number.  I am going to turn that off
the next time we are there.  If this is still on the ng, I will respind
with the results.  The biggie is the notifier to Firelite link.

thanks,

john