Re: FCI 7200 Fire Panel



On Feb 11, 12:08=A0am, Frank Kurz <t...@xxxxxxxxxxxxx> wrote:
> On 10/02/2011 7:50 PM, James B wrote:
>
>
>
>
>
> > On Feb 10, 5:30 pm, Jim<alarmi...@xxxxxxx> =A0wrote:
> >> On Feb 10, 6:34 pm, mleuck<m.le...@xxxxxxxxx> =A0wrote:
>
> >>> On Feb 9, 11:45 pm, Frank Kurz<t...@xxxxxxxxxxxxx> =A0wrote:
>
> >>>> On 09/02/2011 11:01 AM, James B wrote:
>
> >>>>> On Feb 9, 12:58 am, Frank Kurz<t...@xxxxxxxxxxxxx> =A0 =A0wrote:
> >>>>>> On 08/02/2011 7:53 PM, James B wrote:
>
> >>>>>>> Does anyone here now how to run autoconfig on this panel? =A0When=
 I try
> >>>>>>> to run it I get an "access denied" message. =A0The 7200 program m=
anual
> >>>>>>> says to log in with the level 4 code to run the config program. =
=A0I
> >>>>>>> have done this, but once it starts the autoconfig about 2 seconds
> >>>>>>> later it comes up with access denied.
>
> >>>>>>> One thing I noticed is the user codes are only 2 digits and the m=
anual
> >>>>>>> says they should be 6, so I think its a 7200 Micro control but im=
 not
> >>>>>>> sure. =A0I contacted a local FCI dealer "the original installer" =
and
> >>>>>>> they told me the panel is no longer made and they are not sure th=
ey
> >>>>>>> have a tech that knows how to program it still. =A0They did say t=
hey
> >>>>>>> would send one out and quoted me 10 hours @135 per hour. =A0I am =
only
> >>>>>>> trying to add 1 monitor module to the system. =A0The current syst=
em only
> >>>>>>> has 5 points on it now. =A0Needles to say the dealer isnt intrest=
ed in
> >>>>>>> such a small task, or helping me out.
>
> >>>>>>> Can anyone tell me the correct procedure for running autoconifg?
>
> >>>>>>> James
>
> >>>>>> There are two possible scenarios here.
>
> >>>>>> 1. =A0You haven't entered the correct password (which is weird bec=
ause it
> >>>>>> should boot you out immediately), or
>
> >>>>>> 2. =A0You haven't followed the correct sequence to get into
> >>>>>> auto-configure. =A0Are you trying to enter programming from the SC=
U or do
> >>>>>> you have a KDU/KDU-L?
>
> >>>>>> --
> >>>>>> Frank Kurzwww.firetechs.net-Hidequotedtext-
>
> >>>>>> - Show quoted text -
>
> >>>>> Frank,
>
> >>>>> It has a KDU, =A0the only thing that is different is when I log in =
and
> >>>>> it asks for a password. =A0The book says it should say "Enter Passw=
ord
> >>>>> 000000" =A0this one is saying "Enter Password 00". =A0I enter the l=
evel 4
> >>>>> password and it accepts it. =A0I have tried a few wrong passwords o=
n
> >>>>> purpose and it rejects them immediately. =A0The panel is not in ala=
rm
> >>>>> when I log in but it does have 1 trouble "Extra Point" this is the
> >>>>> point I am tryiing to add.
>
> >>>>> James
>
> >>>> Level four password is 440000. =A0The programming sequence is really
> >>>> specific and straight forward. =A0If you need the manual, I can send=
 it to
> >>>> you. =A0Unless the password has been changed by the "installing comp=
any"
> >>>> (which is not uncommon), you should be able to configure the system.
> >>>> Give me a call later in the morning. =A0I'll be in the office after =
1100
> >>>> hours (Pacific). =A0The 800 number is at the bottom of every page on=
 our
> >>>> website.
>
> >>>> --
> >>>> Frank Kurzwww.firetechs.net
>
> >>> Hey Frank, do you have any idea if the OP is even qualified to work o=
n
> >>> a fire panel? I realize he has a program manual but other than that
> >>> you have no idea what his abilities are and it IS a fire panel...-
>
> >> I was thinking the same thing.
>
> >> " But ..... but ..... yer Honor, I know all those people died, but
> >> some guy on the Internet told me it was alright to do it!"- Hide quote=
d text -
>
> >> - Show quoted text -
>
> > Relax you 2, of course im qualified to work on fire systems I am not a
> > dealer for FCI though. You can confirm it here if you feel the need.
>
> > =A0 =A0http://publicsafety.utah.gov/firemarshal/documents/FireAlarmCert=
ifica...
>
> > Frank, when it asks me for a password it is only a 2 digit spot. =A0Is
> > there a way to make it accept a 6 digit code?
>
> > Thanks,
>
> > =A0 James
>
> Yep. =A0One of the more common abbreviations used in this group is "RTFM"=
.
> =A0 In your case it looks like the system isn't responding in accordance
> with the published instructions. =A0The display should emulate what's in
> the manual. =A0You may have a bigger problem!
>
> --
> Frank Kurzwww.firetechs.net- Hide quoted text -
>
> - Show quoted text -

Thanks,  I found a different manual for the 7200 micro panel and it
matches what I have.  "it shows 2 digit codes" However the programming
process is still the same.  Im going to try powering the system down
to do a hard reset.  If that dont work it will be time for an upgrade.

Thanks for your help.

James