Re: Ademco 6139 with 5827BD Keypad
Hi Marc ,
Yes all that works
Address 6139 as 16 if you address it anything other than that like 17
enable *190 10
For 5800TM cut the red jumper , for 5882 receiver all dips are to off.
For 5827 to work just enable fields 24 as 10 in panel.
Also do not mix with 6150rf Either you use 5882 + 5800TM or simply
61550rf
Regards,
Neo
On Oct 1, 1:40 pm, Marc <mlipovi...@xxxxxxx> wrote:
> Anyone gotten one of these to work? I realize the 6139 (older version
> I think-longer vertical than horizontal), have the panel set to address
> 16 where there is a visible display (28,29,30 = no display). Tried
> cutting jumpers on the 5800TM transmitter to changes the addresses
> mentioned above, and making the panel non-addressable by setting to 31
> (=no display condition). It is an ADT branded panel used witha Vista
> 20P board, and seems to wrok just fine otherwise. Also using the 5882
> remote RF receiver (I think it's the Canadian version, but works with
> all transmitters I tried it with, door/window, smoke alarm, glassbreak,
> etc.....also works fine with 5827BD except for indication of armed
> status if I change the panel to a 6150 non-alpha keypad).
>
> This one is driving me crazy, maybe thinking of going to a more
> advanced keypad anyways. Picked up the 6139 cheap at a GoodWill thrift
> store for a buck, and it does allow me to program the system....Any
> help/advice appreciated!
>
> Marc