ABLE_1 wrote:
> Would it not be possible to power the smokes in the rooms from an Aux. Power
> Supply and leave it at that.

Yes.  I would suggest a *supervised* auxiliary power supply and use
power supervision relays (if you're going to monitor smoke status in the
room).  GE makes a DC powered four wire smoke alarm with integral PSR.
The AHJ will often want a system heat detector in each room the GE 448
series smoke alarm will meet this requirement.


> The smokes in the halls and common areas
> would be zoned and give a general alarm which would signal the horn/strobes
> through out the building including the rooms.
>
> Would this not meet the need for local in each room and general
> everywhere???