Thats how DC smoke detectors work. Unless something has changed, only
110V smoke detectors all sound off at the same time. To get a DC smoke
to auto reset is a violation of NFPA72. You can setup the zone to verify
  the alarm, but as far as auto reset without a panel reset breaks some
NFPA72 rules I believe.

Try Firex and Hochiki smokes.

Jim Rojas


ABLE_1 wrote:
> Jim,
>
> I already had checked System Sensor and ESL but could not find any that will
> meet the requirements that I would like.
>
> This is kind of a unusual situation.
>
> I am being asked to install a fire alarm system in a 3 story motel.  The
> owner is requesting that the smokes in each room only alert in that room
> only but be auto-reset rather than system reset.
>
> I initially thought that would be possible but once I started the search for
> such a detector I started to hit walls.  I would rather not have to install
> 115v smokes into this project if I don't have to.
>
> * * * *     Hey Nick are you reading this.  If anyone knows, Nick will know.
>
> Thoughts or suggestions gracefully accepted.
>
> Have a good weekend all.
>
> Les
>
>
>
>
>
>
>> System sensor make some good smokes in many flavors.
>>
>> Jim Rojas
>
>