The UK Home Automation Archive

Archive Home
Group Home
Search Archive


Advanced Search

The UKHA-ARCHIVE IS CEASING OPERATIONS 31 DEC 2024

Latest message you have seen: RE: Re: BARGAIN ALERT


[Message Prev][Message Next][Thread Prev][Thread Next][Message Index][Thread Index]

Re: Cat 5 cable




I think the rating of a CAT5e cable is something like 250-300mA so if you
power each one via one pair each you should just about be ok with (333mA)
per wire.  But as the water pressure is unlikely to allow more than one
irrigation valve on at a time it might be best to have 6 wire 1 to each
valve and the 2 for the ground.

I use Cat5e to power my 12v valve which I think are about 250mA as does Ian
Bird I believe..

S.



"Steve Jones"
<email@stevej        To:     <ukha_d@xxxxxxx>
ones.org>            cc:
Subject:     [ukha_d] Cat 5 cable
27/04/2004
08:17
Please
respond to
ukha_d






I want to connect six solenoid valves for my irrigation system via cat 5
cable.  The total load is 2 amps @ 24volt DC over a cable run of 10 metres.

Will this cable be ok for this?


Regards


Steve Jones
mailto:email@xxxxxxx




[Non-text portions of this message have been removed]



UK Home Automation Meet 2004 - BOOK NOW!
http://www.ukha2004.com

http://www.automatedhome.co.uk

Member Offers - http://www.freeranger.co.uk/ukha

UKHA_D Main Index | UKHA_D Thread Index | UKHA_D Home | Archives Home

Comments to the Webmaster are always welcomed, please use this contact form . Note that as this site is a mailing list archive, the Webmaster has no control over the contents of the messages. Comments about message content should be directed to the relevant mailing list.